Technical Specifications Cable Entry 1 x plastic cable glands M25, 1 x M25 plastic Ex-screw plug Connecting Terminals 2 x 1.5 – 4.0 mm² Current (A) 16A Voltage (V) 200-250V Frequency up to 400 Hz Material Glass-fibre reinforced polyester Ingress Protection (IP) rating IP66 Operating Temperature -20 °C up to +55 °C Colour Black International approvals
 Nickel-plated contacts Low insertion force Safety standard IP66 applies also in the plugged-in state Full AC-3 switching ability Self-cleaning lamellar contacts, low transition resistance All-pole on/off switching Easy plugging
GHG 511 4306 R0001 16A 230V 3Pole 6H Ex-wall Socket (1xM25 cable entry)
GH hazardous, heavy duty IEC 60309 devices are used where hazardous gases may be present, and in areas prone to dust, dirt, vibration, hard use and abuse. Also used in locations where complete protection against water jets and even temporary flooding is required, or in corrosive environments caused by chemicals, atmospheres and water. Commonly used in chemical plants, mining, drilling and steel/grain/flour mills. The plugs and sockets GHG 511 are suitable for use in Zones 1 and 2 as well as in Zones 21 and 22 in accordance with IEC/EN 60079-10-1 and IEC/EN 60079-10-2.